Power Strip-20A, 3 Circuits, Pass-thru Remote Control, 3 Duplex (1 unswtchd), Hardwired, 6ft flexible-conduit

Model: ACS-2006-3C-RPCP-HW

  • Outlets: Total of three (3) NEMA 5-20R duplex outlets
  • Power Rating: 120VAC 60Hz 20A each circuit
  • Unswitched Circuits: One unswitched circuit is always on (1 duplex).
  • Switched Circuits: Two switched circuits (1 duplex each) are controlled by an external sequencer. Each circuit has its own DIP switch to set its position in the sequencing order (1, 2, 3, or 4). Set one (and only one) step for each circuit.
  • Pass-through RJ45 Jacks:
Compare
Project List
Product Info
Tech Specs
Documents
Three-circuit, 20A power strip with Remote Power Control is engineered for applications where multiple AC power circuits and the convenience of controlling AC distribution from a remote location is specified or required. This unit features pass-through connections and requires a compatible sequencer for activation (SEQ-P4 or SEQR-P4).
  • Outlets: Total of three (3) NEMA 5-20R duplex outlets
  • Power Rating: 120VAC 60Hz 20A each circuit
  • Unswitched Circuits: One unswitched circuit is always on (1 duplex).
  • Switched Circuits: Two switched circuits (1 duplex each) are controlled by an external sequencer. Each circuit has its own DIP switch to set its position in the sequencing order (1, 2, 3, or 4). Set one (and only one) step for each circuit.
  • Pass-through RJ45 Jacks:
  • The switched circuits are internally connected to the RJ45 jacks and will therefore be controlled by the external sequencer when it's connected to either jack (using Cat5/6 cable, not included).
  • The RJ45 jacks can be used to daisy chain compatible remote power controls or relays (up to 20 devices per step). See RPC-P or RY-P Series on last page.
  • Surge Protection: Each of the two switched circuits includes surge protection – the unswitched circuit is not protected.
  • Maximum Surge Current: 10,000A
  • VPR: 400V
  • Response Time: 1 nanosecond
  • EMI/RFI Noise Reduction: 20Db at 100kHz
  • Protection Mode: Line to Neutral
  • Ground Contamination: None
  • Chassis: 30 x 2 x 2 inch steel chassis with black powder epoxy finish.
  • Non-metallic Flexible Conduit: Terminates to six ft. flexible conduit with pigtail leads tagged for circuit identification. Conduit can be trimmed in the field as needed.
  • Mounting Brackets: Universal mounting brackets provide versatility allowing the outlets to face forward, center or rear of rack. Minimal rack panel space required = 33.25 inch (19U).
 